Inside Prometheus: Meta’s Journey to a Gigawatt-Scale Supercluster

Source
engineering.fb.com
Date
Why it matters

Shows what a gigawatt-scale training site takes (closed-loop liquid cooling, goodput above 85%), informing how practitioners think about future frontier model capacity and cost.

Key takeaways · AI-distilled
  • Meta reports more than 85% goodput on Muse Wonder runs and more than 90% on RL runs, with a mean time between interruptions of about 47k GPU hours, since raised above 54K GPU hours through fleet firmware fixes.
  • Each NVL72 rack runs a 64-GPU slice and keeps eight GPUs as in-rack spares, so a failed GPU is swapped and the job restarts from checkpoint. With about 2% spare racks, a 32,768-GPU run needs 523 racks, about 13% above the active footprint.
  • Meta says interruptions peaked near 1,000 events per 8K GPUs per day in mid-2025 and fell 99% over a year. NVLink signal integrity across 600,000+ connections was the main early bottleneck on GB200; the target is two per 8K GPUs per day.
  • Synchronized training swings cluster power by 30-40%, and starting or pausing a large job can shift tens of megawatts in seconds. Meta's Dynamo Dimmer lowers GPU power caps gradually near the electrical ceiling instead of stopping jobs.
  • Meta deployed its GB200 racks with 800G of scale-out per GPU rather than 400G, because GB200 raised compute and memory bandwidth over H100 while per-GPU scale-out bandwidth would otherwise have stayed flat.
Terms in this piece · Glossary
  • pretraining — The first, biggest phase of building a model: training it on enormous amounts of text so it learns language, facts, and reasoning in general.
Read the source engineering.fb.com
Recommended reads